Contact details- AU: 1800 633 040 NZ: 0800 633 040 INT: +61 7 55353217

You have no items in your shopping cart.

Our location has changed. Click here to view details.

Signal Conditioners/Limit Alarm

List  Grid 

13 Item(s)

per page
Product Code Product Name QTY Price ($AUD) Action
FC-11 4-20mA Signal Isolator
$246.00
FC-33 DC Volts/mA Signal Conditioner
$314.00
FC-ISO-C Encoder signal conditioner ope
$240.00
FC-ISO-D Encoder signal conditioner dif
$242.00
FC-R1 RTD to 4-20mA Converter
$316.00
FC-T1 T/C to 4-20mA Converter
$313.00
FC-B34 Signal conditioner unipolar
$358.00
FC-35B Signal conditioner bipolar out
$359.00
FC-P3 Signal conditioner
$312.00
FC-3RLY4 Limit Alarm
$306.00
FA-DCDC-1 DC Converter +/-5VDC +/-10VDC
$194.00
FC-5MM Terminal block, replacement, 5 mm. Package of 5. For use with FC series signal conditioners.
$37.00
FC-35MM Terminal block, replacement, 3.5 mm. Package of 14. For use with FC series signal conditioners.
$67.00

List  Grid 

13 Item(s)

per page

Signal Conditioners - DC Voltage, Current or Potentiometer Input

FC Series Signal Conditioners and Signal Isolators
  • FC-11 Loop-Powered Signal Conditioner
  • FC-33 Voltage and Current Signal Conditioner
  • FC-B34 Bipolar Voltage to Unipolar Voltage or Current Signal Conditioner
  • FC-35B Unipolar Voltage or Current to Bipolar Voltage Signal Conditioner
  • FC-P3 Potentiometer Input, Analog Output Signal Conditioner

Loop-powered signal conditioner and signal isolator

FC-11

FC-11 4-20 mA Isolated Signal Conditioner 

Loop-powered signal conditioner and signal isolator for 4-20 mA signal. DIN-rail mountable.

  • The FC-11 is a DIN-rail or side mount, 4-20 mA input / output loop powered signal conditioner with 1500 VDC isolation between input and output and has a user-selectable factory calibration.

  • The output is also calibrated with OFFSET (zero) and SPAN (full scale) adjustments. The OFFSET and SPAN have an adjustment range of 2% of full scale input. 

  • The FC-11 isolated input/ output signal conditioner is useful in eliminating ground loops or sinking/ sourcing issues when interfacing to PLC analog input modules and solves many types of configuration problems. 

DC selectable signal conditioner

FC-33

FC-33 DC Selectable Signal Conditioner 

Signal conditioner and signal isolator for voltage and current signals. 24 VDC input power. Selectable ranges from 0-10 VDC to 0-20mA.

  • The FC-33 is a DIN-rail mount, selectable input/ output signal conditioner with 1500 VDC isolation between input and output and 1500 VDC isolation from 24 volt power and input/ output. The field configurable input/ output types allow a wide ranging capability for 0 - 5 V, 0 - 10 V, 0 - 20 mA, 4 - 20 mA. 

  • The FC-33 has user selectable factory-calibration, but also has OFFSET (zero) and SPAN (full scale) adjustments of the output signal. The OFFSET (zero) has an adjustment range of 0 to 25% of full scale input, the SPAN (full scale) has an adjustment of -20% to 2%. 

  • The FC-33 field configurable isolated input/ output signal conditioner is useful in eliminating ground loops and interfacing sensors to PLC analog input modules. The FC-33 has 3-way isolation that solves many types of configuration problems. 

Bipolar Voltage to Unipolar Voltage or Current Signal Conditioner

FC-34

FC-B34 Bipolar Voltage to Unipolar Voltage or Current Signal Conditioner 

The FC-B34 is a 35mm DIN-rail or side-mount, selectable bipolar input to unipolar output signal conditioner with isolation between input and output, and isolation between 24-volt power and input/output.

  • The FC-B34 field configurable isolated signal conditioner is useful in eliminating ground loops and interfacing sensors to PLC analog input modules. It translates bipolar voltage input to unipolar voltage output or bipolar voltage input to a current output.

  • The input and output signal levels are selected via DIP switches. In addition, the outputs can be either a direct conversion of the inputs or an inversion (a reverse acting operation). 

  • The user also has the option of customizing the input OFFSET (zero) and SPAN (full scale) adjustments that can be set to a percentage of the full scale via a pushbutton on the front panel. 

Unipolar Voltage or Current to Bipolar Voltage Signal Conditioner

FC-35B

FC-35B Unipolar Voltage or Current to Bipolar Voltage Signal Conditioner 

The FC-35B is a 35mm DIN-rail or side-mount, selectable unipolar input to bipolar output signal conditioner with isolation between input and output, and isolation between 24-volt power and input/output.

  • The FC-35B field configurable isolated signal conditioner is useful in eliminating ground loops and interfacing sensors to PLC analog input modules. It translates unipolar voltage inputs or current inputs to bipolar voltage outputs.

  • The input and output signal levels are selected via DIP switches. In addition, the outputs can be either a direct conversion of the inputs or an inversion (a reverse acting operation). 

  • The user also has the option of customizing the input OFFSET (zero) and SPAN (full scale) adjustments that can be set to a percentage of the full scale via a pushbutton on the front panel. 

Potentiometer Input, Analog Output Signal Conditioner

FC-P3

FC-P3 Potentiometer Input, Analog Output Signal Conditioner 

The FC-P3 is a resistive input to isolated analog output signal conditioner. The input resistive range (high end resistivity, low end resistivity) is set through the use of a pushbutton programming routine.

  • The FC-P3 is field configurable for 3-wire potentiometer/slide-wire inputs with end-to-end resistance ranges from 0-100 ohms to 0-100 kilohms. The input adjustment range can be scaled down to a minimum of 10% of the potentiometer being used.

  • Switch selectable, analog output options include 0-20 mA, 4-20 mA, 0-5V, and 0-10 V. The PGM LED provides an indication of operating status and is used during the field programming process.

  • The MAX and MIN LED's indicate OVER and UNDER range status. The module can be 35 mm DIN rail or side mounted and is UL listed. Power for the unit is provided by a customer supplied 24 VAC or 24 VDC Class 2 power supply. 

 

FC Series Signal Conditioners Overview 

FC Series Bipolar Signal Conditioners Overview